Vulnerabilities (CVE)

Filtered by vendor Abb Subscribe
Total 150 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-24674 1 Abb 2 Symphony \+ Historian, Symphony \+ Operations 2021-10-07 9.0 HIGH 8.8 HIGH
In S+ Operations and S+ Historian, not all client commands correctly check user permission as expected. Authenticated but Unauthorized remote users could execute a Denial-of-Service (DoS) attack, execute arbitrary code, or obtain more privilege than intended on the machines.
CVE-2020-24677 1 Abb 2 Symphony \+ Historian, Symphony \+ Operations 2021-10-07 6.5 MEDIUM 8.8 HIGH
Vulnerabilities in the S+ Operations and S+ Historian web applications can lead to a possible code execution and privilege escalation, redirect the user somewhere else or download unwanted data.
CVE-2020-24673 1 Abb 2 Symphony \+ Historian, Symphony \+ Operations 2021-10-07 7.5 HIGH 9.8 CRITICAL
In S+ Operations and S+ Historian, a successful SQL injection exploit can read sensitive data from the database, modify database data (Insert/Update/Delete), execute administration operations on the database (such as shutdown the DBMS), recover the content of a given file present on the DBMS file system and in some cases issue commands to the operating system. This can lead to a loss of confidentiality and data integrity or even affect the product behavior and its availability.
CVE-2021-22276 1 Abb 10 System Access Point 127v, System Access Point 127v Firmware, System Access Point 2.0 and 7 more 2021-10-06 4.3 MEDIUM 5.5 MEDIUM
The vulnerability allows a successful attacker to bypass the integrity check of FW uploaded to the free@home System Access Point.
CVE-2020-24676 1 Abb 2 Symphony \+ Historian, Symphony \+ Operations 2021-09-14 4.6 MEDIUM 7.8 HIGH
In Symphony Plus Operations and Symphony Plus Historian, some services can be vulnerable to privilege escalation attacks. An unprivileged (but authenticated) user could execute arbitrary code and result in privilege escalation, depending on the user that the service runs as.
CVE-2020-8481 1 Abb 1 800xa System 2021-09-14 10.0 HIGH 9.8 CRITICAL
For ABB products ABB Ability™ System 800xA and related system extensions versions 5.1, 6.0 and 6.1, Compact HMI versions 5.1 and 6.0, Control Builder Safe 1.0, 1.1 and 2.0, Symphony Plus -S+ Operations 3.0 to 3.2 Symphony Plus -S+ Engineering 1.1 to 2.2, Composer Harmony 5.1, 6.0 and 6.1, Melody Composer 5.3, 6.1/6.2 and SPE for Melody 1.0SPx (Composer 6.3), Harmony OPC Server (HAOPC) Standalone 6.0, 6.1 and 7.0, ABB Ability™ System 800xA/ Advant® OCS Control Builder A 1.3 and 1.4, Advant® OCS AC100 OPC Server 5.1, 6.0 and 6.1, Composer CTK 6.1 and 6.2, AdvaBuild 3.7 SP1 and SP2, OPCServer for MOD 300 (non-800xA) 1.4, OPC Data Link 2.1 and 2.2, Knowledge Manager 8.0, 9.0 and 9.1, Manufacturing Operations Management 1812 and 1909, confidential data is written in an unprotected file. An attacker who successfully exploited this vulnerability could take full control of the computer.
CVE-2020-11420 2 Abb, Generex 4 Cs141, Cs141 Firmware, Cs141 and 1 more 2021-09-14 4.0 MEDIUM 6.5 MEDIUM
UPS Adapter CS141 before 1.90 allows Directory Traversal. An attacker with Admin or Engineer login credentials could exploit the vulnerability by manipulating variables that reference files and by doing this achieve access to files and directories outside the web root folder. An attacker may access arbitrary files and directories stored in the file system, but integrity of the files are not jeopardized as attacker have read access rights only.
CVE-2019-19106 2 Abb, Busch-jaeger 4 Tg\/s3.2, Tg\/s3.2 Firmware, 6186\/11 and 1 more 2021-09-14 6.4 MEDIUM 9.1 CRITICAL
Improper implementation of Access Control in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows an unauthorized user to access data marked as restricted, such as viewing or editing user profiles and application settings.
CVE-2020-24686 1 Abb 12 Pm554, Pm554 Firmware, Pm556 and 9 more 2021-03-05 5.0 MEDIUM 7.5 HIGH
The vulnerabilities can be exploited to cause the web visualization component of the PLC to stop and not respond, leading to genuine users losing remote visibility of the PLC state. If a user attempts to login to the PLC while this vulnerability is exploited, the PLC will show an error state and refuse connections to Automation Builder. The execution of the PLC application is not affected by this vulnerability. This issue affects ABB AC500 V2 products with onboard Ethernet.
CVE-2020-24685 1 Abb 3 Ac500 Cpu Firmware, Pm573-eth, Pm583-eth 2021-02-16 5.0 MEDIUM 8.6 HIGH
An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.
CVE-2019-18997 1 Abb 1 Pb610 Panel Builder 600 2020-10-22 5.0 MEDIUM 7.5 HIGH
The HMISimulator component of ABB PB610 Panel Builder 600 uses the readFile/writeFile interface to manipulate the work file. Path configuration in PB610 HMISimulator versions 2.8.0.424 and earlier potentially allows access to files outside of the working directory, thus potentially supporting unauthorized file access.
CVE-2020-10287 1 Abb 4 Irb140, Irb140 Firmware, Irc5 and 1 more 2020-07-24 7.5 HIGH 9.8 CRITICAL
The IRC5 family with UAS service enabled comes by default with credentials that can be found on publicly available manuals. ABB considers this a well documented functionality that helps customer set up however, out of our research, we found multiple production systems running these exact default credentials and consider thereby this an exposure that should be mitigated. Moreover, future deployments should consider that these defaults should be forbidden (user should be forced to change them).
CVE-2020-10288 2 Abb, Windriver 4 Irb140, Irc5, Robotware and 1 more 2020-07-23 7.5 HIGH 9.8 CRITICAL
IRC5 exposes an ftp server (port 21). Upon attempting to gain access you are challenged with a request of username and password, however you can input whatever you like. As long as the field isn't empty it will be accepted.
CVE-2020-8471 1 Abb 3 800xa System, Compact Hmi, Control Builder Safe 2020-06-09 4.6 MEDIUM 7.8 HIGH
For the Central Licensing Server component used in ABB products ABB Ability™ System 800xA and related system extensions versions 5.1, 6.0 and 6.1, Compact HMI versions 5.1 and 6.0, Control Builder Safe 1.0, 1.1 and 2.0, Symphony Plus -S+ Operations 3.0 to 3.2 Symphony Plus -S+ Engineering 1.1 to 2.2, Composer Harmony 5.1, 6.0 and 6.1, Melody Composer 5.3, 6.1/6.2 and SPE for Melody 1.0SPx (Composer 6.3), Harmony OPC Server (HAOPC) Standalone 6.0, 6.1 and 7.0, ABB Ability™ System 800xA/ Advant® OCS Control Builder A 1.3 and 1.4, Advant® OCS AC100 OPC Server 5.1, 6.0 and 6.1, Composer CTK 6.1 and 6.2, AdvaBuild 3.7 SP1 and SP2, OPCServer for MOD 300 (non-800xA) 1.4, OPC Data Link 2.1 and 2.2, Knowledge Manager 8.0, 9.0 and 9.1, Manufacturing Operations Management 1812 and 1909, weak file permissions allow an authenticated attacker to block the license handling, escalate his/her privileges and execute arbitrary code.
CVE-2020-8482 1 Abb 1 Device Library Wizard 2020-06-01 2.1 LOW 5.5 MEDIUM
Insecure storage of sensitive information in ABB Device Library Wizard versions 6.0.X, 6.0.3.1 and 6.0.3.2 allows unauthenticated low privilege user to read file that contains confidential data
CVE-2020-8473 1 Abb 1 800xa Base System 2020-05-14 6.8 MEDIUM 7.8 HIGH
Insufficient folder permissions used by system functions in ABB System 800xA Base (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploit the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications.
CVE-2020-8472 1 Abb 5 Ac800m, Base Software, Control Builder M and 2 more 2020-05-14 6.8 MEDIUM 7.8 HIGH
Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base Software for SoftControl (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploited the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications.
CVE-2020-8478 1 Abb 4 Ac800m, Base Software, Mms Server and 1 more 2020-05-13 2.1 LOW 3.3 LOW
Insufficient protection of the inter-process communication functions in ABB System 800xA products OPC Server for AC 800M, MMS Server for AC 800M and Base Software for SoftControl (all published versions) enables an attacker authenticated on the local system to inject data, affecting the online view of runtime data shown in Control Builder.
CVE-2020-8489 1 Abb 1 800xa Information Management 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA Information Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting the runtime values to be stored in the archive, or making Information Management history services unavailable.
CVE-2020-8488 1 Abb 1 800xa Batch Management 2020-05-08 4.6 MEDIUM 7.8 HIGH
Insufficient protection of the inter-process communication functions in ABB System 800xA Batch Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting User Interface update during batch execution and/or compare/printing functionalities.