CVE-2020-7531 1 Schneider-electric 1 Scadapack 7x Remote Connect 2020-09-21 6.8 MEDIUM 7.8 HIGH
A CWE-284 Improper Access Control vulnerability exists in SCADAPack 7x Remote Connect (V3.6.3.574 and prior) which allows an attacker to place executables in a specific folder and run code whenever RemoteConnect is executed by the user.
CVE-2020-7532 1 Schneider-electric 1 Scadapack X70 Security Administrator 2020-09-21 6.8 MEDIUM 7.8 HIGH
A CWE-502 Deserialization of Untrusted Data vulnerability exists in SCADAPack x70 Security Administrator (V1.2.0 and prior) which could allow arbitrary code execution when an attacker builds a custom .SDB file containing a malicious serialized buffer.
CVE-2018-1124 6 Canonical, Debian, Opensuse and 3 more 9 Ubuntu Linux, Debian Linux, Leap and 6 more 2020-09-09 4.6 MEDIUM 7.8 HIGH
procps-ng before version 3.3.15 is vulnerable to multiple integer overflows leading to a heap corruption in file2strvec function. This allows a privilege escalation for a local attacker who can create entries in procfs by starting processes, which could result in crashes or arbitrary code execution in proc utilities run by other users.
CVE-2020-7521 1 Schneider-electric 1 Apc Easy Ups Online Software 2020-09-04 7.5 HIGH 9.8 CRITICAL
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in SFAPV9601 - APC Easy UPS On-Line Software (V2.0 and earlier) when accessing a vulnerable method of `FileUploadServlet` which may lead to uploading executable files to non-specified directories.
CVE-2020-7522 1 Schneider-electric 1 Apc Easy Ups Online Software 2020-09-04 7.5 HIGH 9.8 CRITICAL
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in SFAPV9601 - APC Easy UPS On-Line Software (V2.0 and earlier) when accessing a vulnerable method of `SoundUploadServlet` which may lead to uploading executable files to non-specified directories.
CVE-2020-7525 1 Schneider-electric 4 Spacelynk, Spacelynk Firmware, Wiser For Knx and 1 more 2020-09-04 5.0 MEDIUM 7.5 HIGH
Improper Restriction of Excessive Authentication Attempts vulnerability exists in all hardware versions of spaceLYnk and Wiser for KNX (formerly homeLYnk) which could allow an attacker to guess a password when brute force is used.
CVE-2020-7527 1 Schneider-electric 1 Somove 2020-09-04 4.6 MEDIUM 7.8 HIGH
Incorrect Default Permission vulnerability exists in SoMove (V2.8.1) and prior which could cause elevation of privilege and provide full access control to local system users to SoMove component and services when a SoMove installer script is launched.
CVE-2018-7793 1 Schneider-electric 4 Foxboro Dcs, Foxboro Evo, Foxview and 1 more 2020-08-24 4.6 MEDIUM 8.7 HIGH
A Credential Management vulnerability exists in FoxView HMI SCADA (All Foxboro DCS, Foxboro Evo, and IA Series versions prior to Foxboro DCS Control Core Services 9.4 (CCS 9.4) and FoxView 10.5.) which could cause unauthorized disclosure, modification, or disruption in service when the password is modified without permission.
CVE-2018-7831 1 Schneider-electric 8 Modicom Bmxnor0200h, Modicom Bmxnor0200h Firmware, Modicom M340 and 5 more 2020-08-24 4.3 MEDIUM 8.8 HIGH
An Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS) vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 allowing an attacker to send a specially crafted URL to a currently authenticated web server user to execute a password change on the web server.
CVE-2018-7803 1 Schneider-electric 1 Triconex Tristation Emulator 2020-08-24 4.3 MEDIUM 5.9 MEDIUM
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in Triconex TriStation Emulator V1.2.0, which could cause the emulator to crash when sending a specially crafted packet. The emulator is used infrequently for application logic testing. It is susceptible to an attack only while running in off-line mode. This vulnerability does not exist in Triconex hardware products and therefore has no effect on the operating safety functions in a plant.
CVE-2019-6815 1 Schneider-electric 2 Modicon Quantum, Modicon Quantum Firmware 2020-08-24 6.4 MEDIUM 9.1 CRITICAL
In Modicon Quantum all firmware versions, CWE-264: Permissions, Privileges, and Access Control vulnerabilities could cause a denial of service or unauthorized modifications of the PLC configuration when using Ethernet/IP protocol.
CVE-2018-7779 1 Schneider-electric 6 Homelynk, Homelynk Firmware, Spacelynk and 3 more 2020-08-24 5.0 MEDIUM 7.5 HIGH
In Schneider Electric Wiser for KNX V2.1.0 and prior, homeLYnk V2.0.1 and prior; and spaceLYnk V2.1.0 and prior, weak and unprotected FTP access could allow an attacker unauthorized access.
CVE-2018-7816 1 Schneider-electric 118 D6220, D6220 Firmware, D6220l and 115 more 2020-08-24 5.5 MEDIUM 6.5 MEDIUM
A Permissions, Privileges, and Access Control vulnerability exists in the web-based GUI of the 1st Gen Pelco Sarix Enhanced Camera that could allow a remote attacker to delete an arbitrary file.
CVE-2018-7814 1 Schneider-electric 1 Guicon 2020-08-24 6.8 MEDIUM 7.8 HIGH
A Stack-based Buffer Overflow (CWE-121) vulnerability exists in Eurotherm by Schneider Electric GUIcon V2.0 (Gold Build 683.0) which could cause remote code to be executed when parsing a GD1 file
CVE-2020-7520 1 Schneider-electric 1 Software Update Utility 2020-07-28 4.0 MEDIUM 4.7 MEDIUM
A CWE-601: URL Redirection to Untrusted Site ('Open Redirect') vulnerability exists in Schneider Electric Software Update (SESU), V2.4.0 and prior, which could cause execution of malicious code on the victim's machine. In order to exploit this vulnerability, an attacker requires privileged access on the engineering workstation to modify a Windows registry key which would divert all traffic updates to go through a server in the attacker's possession. A man-in-the-middle attack is then used to complete the exploit.
CVE-2020-7517 1 Schneider-electric 1 Easergy Builder 2020-07-27 2.1 LOW 5.5 MEDIUM
A CWE-312: Cleartext Storage of Sensitive Information vulnerability exists in Easergy Builder (Version 1.4.7.2 and older) which could allow an attacker to read user credentials.
CVE-2020-7518 1 Schneider-electric 1 Easergy Builder 2020-07-27 5.0 MEDIUM 7.5 HIGH
A CWE-20: Improper input validation vulnerability exists in Easergy Builder (Version 1.4.7.2 and older) which could allow an attacker to modify project configuration files.
CVE-2020-7514 1 Schneider-electric 1 Easergy Builder 2020-07-27 4.6 MEDIUM 7.8 HIGH
A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists in Easergy Builder (Version 1.4.7.2 and older) which could allow an attacker access to the authorization credentials for a device and gain full access.
CVE-2020-7519 1 Schneider-electric 1 Easergy Builder 2020-07-27 5.0 MEDIUM 7.5 HIGH
A CWE-521: Weak Password Requirements vulnerability exists in Easergy Builder (Version 1.4.7.2 and older) which could allow an attacker to compromise a user account.
CVE-2012-0931 1 Schneider-electric 1 Modicon Quantum Plc 2020-07-23 7.5 HIGH 9.8 CRITICAL
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.