Filtered by vendor Schneider-electric
Subscribe
Total
757 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2021-22783 | 1 Schneider-electric | 1 Ritto Wiser Door | 2022-03-12 | 4.8 MEDIUM | 7.6 HIGH |
| A CWE-200: Information Exposure vulnerability exists which could allow a session hijack when the door panel is communicating with the door. Affected Product: Ritto Wiser Door (All versions) | |||||
| CVE-2022-22813 | 1 Schneider-electric | 66 Easergy P141, Easergy P141 Firmware, Easergy P142 and 63 more | 2022-02-28 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-798: Use of Hard-coded Credentials vulnerability exists. If an attacker were to obtain the TLS cryptographic key and take active control of the Courier tunneling communication network, they could potentially observe and manipulate traffic associated with product configuration. | |||||
| CVE-2022-22724 | 1 Schneider-electric | 12 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 9 more | 2022-02-25 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions) | |||||
| CVE-2021-22796 | 1 Schneider-electric | 1 C-gate Server | 2022-02-23 | 6.8 MEDIUM | 7.8 HIGH |
| A CWE-287: Improper Authentication vulnerability exists that could allow remote code execution when a malicious file is uploaded. Affected Product: C-Bus Toolkit (V1.15.9 and prior), C-Gate Server (V2.11.7 and prior) | |||||
| CVE-2021-22748 | 1 Schneider-electric | 1 C-bus Toolkit | 2022-02-23 | 6.5 MEDIUM | 8.8 HIGH |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could allow a remote code execution when a file is saved. Affected Product: C-Bus Toolkit (V1.15.9 and prior), C-Gate Server (V2.11.7 and prior) | |||||
| CVE-2021-22806 | 1 Schneider-electric | 6 Fellerlynk, Fellerlynk Firmware, Spacelynk and 3 more | 2022-02-22 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-669: Incorrect Resource Transfer Between Spheres vulnerability exists that could cause data exfiltration and unauthorized access when accessing a malicious website. Affected Product: spaceLYnk (V2.6.1 and prior), Wiser for KNX (V2.6.1 and prior), fellerLYnk (V2.6.1 and prior) | |||||
| CVE-2021-22801 | 1 Schneider-electric | 1 Connexium Network Manager | 2022-02-22 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-269: Improper Privilege Management vulnerability exists that could cause an arbitrary command execution when the software is configured with specially crafted event actions. Affected Product: ConneXium Network Manager Software (All Versions) | |||||
| CVE-2021-22824 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in denial of service, due to missing length check on user-supplied data from a constructed message received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 and prior) | |||||
| CVE-2021-22823 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 5.0 MEDIUM | 9.1 CRITICAL |
| A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 and prior) | |||||
| CVE-2021-22805 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 5.0 MEDIUM | 9.1 CRITICAL |
| A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) | |||||
| CVE-2021-22802 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) | |||||
| CVE-2021-22803 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists that could lead to remote code execution through a number of paths, when an attacker, writes arbitrary files to folders in context of the DC module, by sending constructed messages on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) | |||||
| CVE-2021-22804 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Collector | 2022-02-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause disclosure of arbitrary files being read in the context of the user running IGSS, due to missing validation of user supplied data in network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) | |||||
| CVE-2021-22800 | 1 Schneider-electric | 2 Modicon M218, Modicon M218 Firmware | 2022-02-18 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-20: Improper Input Validation vulnerability exists that could cause a Denial of Service when a crafted packet is sent to the controller over network port 1105/TCP. Affected Product: Modicon M218 Logic Controller (V5.1.0.6 and prior) | |||||
| CVE-2022-24318 | 1 Schneider-electric | 3 Clearscada, Ecostruxure Geo Scada Expert 2019, Ecostruxure Geo Scada Expert 2020 | 2022-02-17 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-326: Inadequate Encryption Strength vulnerability exists that could cause non-encrypted communication with the server when outdated versions of the ViewX client are used. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions) | |||||
| CVE-2022-24317 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2022-02-17 | 5.0 MEDIUM | 7.5 HIGH |
| A CWE-862: Missing Authorization vulnerability exists that could cause information exposure when an attacker sends a specific message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | |||||
| CVE-2022-24313 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2022-02-17 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | |||||
| CVE-2022-24312 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2022-02-17 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by adding at end of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | |||||
| CVE-2022-24311 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2022-02-17 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause modification of an existing file by inserting at beginning of file or create a new file in the context of the Data Server potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | |||||
| CVE-2022-24310 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2022-02-17 | 7.5 HIGH | 9.8 CRITICAL |
| A CWE-190: Integer Overflow or Wraparound vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) | |||||