Filtered by vendor Mitsubishielectric
Subscribe
Total
158 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2023-5274 | 1 Mitsubishielectric | 1 Gx Works2 | 2023-12-05 | N/A | 4.7 MEDIUM |
Improper Input Validation vulnerability in simulation function of GX Works2 allows an attacker to cause a denial-of-service (DoS) condition on the function by sending specially crafted packets. However, the attacker would need to send the packets from within the same personal computer where the function is running. | |||||
CVE-2023-5275 | 1 Mitsubishielectric | 1 Gx Works2 | 2023-12-05 | N/A | 4.7 MEDIUM |
Improper Input Validation vulnerability in simulation function of GX Works2 allows an attacker to cause a denial-of-service (DoS) condition on the function by sending specially crafted packets. However, the attacker would need to send the packets from within the same personal computer where the function is running. | |||||
CVE-2021-20590 | 1 Mitsubishielectric | 12 Got2000 Gt25, Got2000 Gt25 Firmware, Got2000 Gt27 and 9 more | 2023-11-07 | 4.3 MEDIUM | 7.5 HIGH |
Improper authentication vulnerability in GOT2000 series GT27 model VNC server versions 01.39.010 and prior, GOT2000 series GT25 model VNC server versions 01.39.010 and prior, GOT2000 series GT21 model GT2107-WTBD VNC server versions 01.40.000 and prior, GOT2000 series GT21 model GT2107-WTSD VNC server versions 01.40.000 and prior, GOT SIMPLE series GS21 model GS2110-WTBD-N VNC server versions 01.40.000 and prior and GOT SIMPLE series GS21 model GS2107-WTBD-N VNC server versions 01.40.000 and prior allows a remote unauthenticated attacker to gain unauthorized access via specially crafted packets when the "VNC server" function is used. | |||||
CVE-2021-20592 | 1 Mitsubishielectric | 7 Got2000 Gt23, Got2000 Gt23 Firmware, Got2000 Gt25 and 4 more | 2023-11-07 | 7.8 HIGH | 7.5 HIGH |
Missing synchronization vulnerability in GOT2000 series GT27 model communication driver versions 01.19.000 through 01.39.010, GT25 model communication driver versions 01.19.000 through 01.39.010 and GT23 model communication driver versions 01.19.000 through 01.39.010 and GT SoftGOT2000 versions 1.170C through 1.256S allows a remote unauthenticated attacker to cause DoS condition on the MODBUS/TCP slave communication function of the products by rapidly and repeatedly connecting and disconnecting to and from the MODBUS/TCP communication port on a target. Restart or reset is required to recover. | |||||
CVE-2020-12007 | 2 Iconics, Mitsubishielectric | 11 Bizviz, Energy Analytix, Facility Analytix and 8 more | 2023-11-07 | 7.5 HIGH | 9.8 CRITICAL |
A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior. | |||||
CVE-2023-4562 | 1 Mitsubishielectric | 380 Fx3g-14 Mr\/ds, Fx3g-14 Mr\/ds Firmware, Fx3g-14 Mr\/es and 377 more | 2023-10-23 | N/A | 9.1 CRITICAL |
Improper Authentication vulnerability in Mitsubishi Electric Corporation MELSEC-F Series main modules allows a remote unauthenticated attacker to obtain sequence programs from the product or write malicious sequence programs or improper data in the product without authentication by sending illegitimate messages. | |||||
CVE-2023-1618 | 1 Mitsubishielectric | 2 Melsec Ws0-geth00200, Melsec Ws0-geth00200 Firmware | 2023-08-23 | N/A | 8.6 HIGH |
Active Debug Code vulnerability in Mitsubishi Electric Corporation MELSEC WS Series WS0-GETH00200 Serial number 2310 **** and prior allows a remote unauthenticated attacker to bypass authentication and illegally log into the affected module by connecting to it via telnet which is hidden function and is enabled by default when shipped from the factory. As a result, a remote attacker with unauthorized login can reset the module, and if certain conditions are met, he/she can disclose or tamper with the module's configuration or rewrite the firmware. | |||||
CVE-2023-3346 | 1 Mitsubishielectric | 42 C80, C80 Firmware, E70 and 39 more | 2023-08-11 | N/A | 9.8 CRITICAL |
Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability in MITSUBSHI CNC Series allows a remote unauthenticated attacker to cause Denial of Service (DoS) condition and execute arbitrary code on the product by sending specially crafted packets. In addition, system reset is required for recovery. | |||||
CVE-2023-3373 | 1 Mitsubishielectric | 4 Gs21, Gs21 Firmware, Gt21 and 1 more | 2023-08-10 | N/A | 9.1 CRITICAL |
Predictable Exact Value from Previous Values vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT21 model versions 01.49.000 and prior and GOT SIMPLE Series GS21 model versions 01.49.000 and prior allows a remote unauthenticated attacker to hijack data connections (session hijacking) or prevent legitimate users from establishing data connections (to cause DoS condition) by guessing the listening port of the data connection on FTP server and connecting to it. | |||||
CVE-2023-0525 | 1 Mitsubishielectric | 14 Gs21, Gs21 Firmware, Gs25 and 11 more | 2023-08-10 | N/A | 7.5 HIGH |
Weak Encoding for Password vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT27 model versions 01.49.000 and prior, GT25 model versions 01.49.000 and prior, GT23 model versions 01.49.000 and prior, GT21 model versions 01.49.000 and prior, GOT SIMPLE Series GS25 model versions 01.49.000 and prior, GS21 model versions 01.49.000 and prior, GT Designer3 Version1 (GOT2000) versions 1.295H and prior and GT SoftGOT2000 versions 1.295H and prior allows a remote unauthenticated attacker to obtain plaintext passwords by sniffing packets containing encrypted passwords and decrypting the encrypted passwords, in the case of transferring data with GT Designer3 Version1(GOT2000) and GOT2000 Series or GOT SIMPLE Series with the Data Transfer Security function enabled, or in the case of transferring data by the SoftGOT-GOT link function with GT SoftGOT2000 and GOT2000 series with the Data Transfer Security function enabled. | |||||
CVE-2022-25156 | 1 Mitsubishielectric | 32 Fx5uc, Fx5uc-32mr\/ds-ts, Fx5uc-32mr\/ds-ts Firmware and 29 more | 2023-08-08 | 6.8 MEDIUM | 8.1 HIGH |
Use of Weak Hash vulnerability in Mitsubishi Electric MELSEC iQ-F series FX5U(C) CPU all versions, Mitsubishi Electric MELSEC iQ-F series FX5UJ CPU all versions, Mitsubishi Electric MELSEC iQ-R series R00/01/02CPU all versions, Mitsubishi Electric MELSEC iQ-R series R04/08/16/32/120(EN)CPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120SFCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PSFCPU all versions, Mitsubishi Electric MELSEC iQ-R series RJ71C24(-R2/R4) all versions, Mitsubishi Electric MELSEC iQ-R series RJ71EN71 all versions, Mitsubishi Electric MELSEC iQ-R series RJ72GF15-T2 all versions, Mitsubishi Electric MELSEC Q series Q03UDECPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/10/13/20/26/50/100UDEHCPU all versions, Mitsubishi Electric MELSEC Q series Q03/04/06/13/26UDVCPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/13/26UDPVCPU all versions, Mitsubishi Electric MELSEC Q series QJ71C24N(-R2/R4) all versions, Mitsubishi Electric MELSEC Q series QJ71E71-100 all versions, Mitsubishi Electric MELSEC Q series QJ72BR15 all versions, Mitsubishi Electric MELSEC Q series QJ72LP25(-25/G/GE) all versions, Mitsubishi Electric MELSEC L series L02/06/26CPU(-P) all versions, Mitsubishi Electric MELSEC L series L26CPU-(P)BT all versions, Mitsubishi Electric MELSEC L series LJ71C24(-R2) all versions, Mitsubishi Electric MELSEC L series LJ71E71-100 all versions and Mitsubishi Electric MELSEC L series LJ72GF15-T2 all versions allows a remote unauthenticated attacker to login to the product by using a password reversed from a previously eavesdropped password hash. | |||||
CVE-2022-25157 | 1 Mitsubishielectric | 32 Fx5uc, Fx5uc-32mr\/ds-ts, Fx5uc-32mr\/ds-ts Firmware and 29 more | 2023-08-08 | 6.4 MEDIUM | 9.1 CRITICAL |
Use of Password Hash Instead of Password for Authentication vulnerability in Mitsubishi Electric MELSEC iQ-F series FX5U(C) CPU all versions, Mitsubishi Electric MELSEC iQ-F series FX5UJ CPU all versions, Mitsubishi Electric MELSEC iQ-R series R00/01/02CPU all versions, Mitsubishi Electric MELSEC iQ-R series R04/08/16/32/120(EN)CPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120SFCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PSFCPU all versions, Mitsubishi Electric MELSEC iQ-R series R16/32/64MTCPU all versions, Mitsubishi Electric MELSEC iQ-R series RJ71C24(-R2/R4) all versions, Mitsubishi Electric MELSEC iQ-R series RJ71EN71 all versions, Mitsubishi Electric MELSEC iQ-R series RJ71GF11-T2 all versions, Mitsubishi Electric MELSEC iQ-R series RJ71GP21(S)-SX all versions, Mitsubishi Electric MELSEC iQ-R series RJ72GF15-T2 all versions, Mitsubishi Electric MELSEC Q series Q03UDECPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/10/13/20/26/50/100UDEHCPU all versions, Mitsubishi Electric MELSEC Q series Q03/04/06/13/26UDVCPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/13/26UDPVCPU all versions, Mitsubishi Electric MELSEC Q series QJ71C24N(-R2/R4) all versions, Mitsubishi Electric MELSEC Q series QJ71E71-100 all versions, Mitsubishi Electric MELSEC L series L02/06/26CPU(-P) all versions, Mitsubishi Electric MELSEC L series L26CPU-(P)BT all versions, Mitsubishi Electric MELSEC L series LJ71C24(-R2) all versions, Mitsubishi Electric MELSEC L series LJ71E71-100 all versions and Mitsubishi Electric MELSEC L series LJ72GF15-T2 all versions allows a remote unauthenticated attacker to disclose or tamper with the information in the product by using an eavesdropped password hash. | |||||
CVE-2022-25155 | 1 Mitsubishielectric | 32 Fx5uc, Fx5uc-32mr\/ds-ts, Fx5uc-32mr\/ds-ts Firmware and 29 more | 2023-08-08 | 6.8 MEDIUM | 8.1 HIGH |
Use of Password Hash Instead of Password for Authentication vulnerability in Mitsubishi Electric MELSEC iQ-F series FX5U(C) CPU all versions, Mitsubishi Electric MELSEC iQ-F series FX5UJ CPU all versions, Mitsubishi Electric MELSEC iQ-R series R00/01/02CPU all versions, Mitsubishi Electric MELSEC iQ-R series R04/08/16/32/120(EN)CPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120SFCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PCPU all versions, Mitsubishi Electric MELSEC iQ-R series R08/16/32/120PSFCPU all versions, Mitsubishi Electric MELSEC iQ-R series RJ71GN11-T2 all versions, Mitsubishi Electric MELSEC iQ-R series RJ71GN11-EIP all versions, Mitsubishi Electric MELSEC iQ-R series RJ71C24(-R2/R4) all versions, Mitsubishi Electric MELSEC iQ-R series RJ71EN71 all versions, Mitsubishi Electric MELSEC iQ-R series RJ72GF15-T2 all versions, Mitsubishi Electric MELSEC Q series Q03UDECPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/10/13/20/26/50/100UDEHCPU all versions, Mitsubishi Electric MELSEC Q series Q03/04/06/13/26UDVCPU all versions, Mitsubishi Electric MELSEC Q series Q04/06/13/26UDPVCPU all versions, Mitsubishi Electric MELSEC Q series QJ71C24N(-R2/R4) all versions, Mitsubishi Electric MELSEC Q series QJ71E71-100 all versions, Mitsubishi Electric MELSEC Q series QJ72BR15 all versions, Mitsubishi Electric MELSEC Q series QJ72LP25(-25/G/GE) all versions, Mitsubishi Electric MELSEC L series L02/06/26CPU(-P) all versions, Mitsubishi Electric MELSEC L series L26CPU-(P)BT all versions, Mitsubishi Electric MELSEC L series LJ71C24(-R2) all versions, Mitsubishi Electric MELSEC L series LJ71E71-100 all versions and Mitsubishi Electric MELSEC L series LJ72GF15-T2 all versions allows a remote unauthenticated attacker to login to the product by replaying an eavesdropped password hash. | |||||
CVE-2021-20612 | 1 Mitsubishielectric | 6 Fx3u-enet, Fx3u-enet-l, Fx3u-enet-l Firmware and 3 more | 2023-08-08 | 7.8 HIGH | 7.5 HIGH |
Lack of administrator control over security vulnerability in MELSEC-F series FX3U-ENET Firmware version 1.14 and prior, FX3U-ENET-L Firmware version 1.14 and prior and FX3U-ENET-P502 Firmware version 1.14 and prior allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition in communication function of the product or other unspecified effects by sending specially crafted packets to an unnecessary opening of TCP port. Control by MELSEC-F series PLC is not affected by this vulnerability, but system reset is required for recovery. | |||||
CVE-2022-33323 | 1 Mitsubishielectric | 102 Rh-12fh55, Rh-12fh55 Firmware, Rh-12fh70 and 99 more | 2023-07-21 | N/A | 7.5 HIGH |
Active Debug Code vulnerability in robot controller of Mitsubishi Electric Corporation industrial robot MELFA SD/SQ Series and MELFA F-Series allows a remote unauthenticated attacker to gain unauthorized access by authentication bypass through an unauthorized telnet login. As for the affected model names, controller types and firmware versions, see the Mitsubishi Electric's advisory which is listed in [References] section. | |||||
CVE-2023-2846 | 1 Mitsubishielectric | 300 Fx3g-14mr\/ds, Fx3g-14mr\/ds Firmware, Fx3g-14mr\/es and 297 more | 2023-07-10 | N/A | 9.1 CRITICAL |
Authentication Bypass by Capture-replay vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series main modules allows a remote unauthenticated attacker to cancel the password/keyword setting and login to the affected products by sending specially crafted packets. | |||||
CVE-2023-1424 | 1 Mitsubishielectric | 78 Melsec Iq-fx5u-32mr\/ds, Melsec Iq-fx5u-32mr\/ds Firmware, Melsec Iq-fx5u-32mr\/dss and 75 more | 2023-07-07 | N/A | 8.1 HIGH |
Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series CPU modules and MELSEC iQ-R Series CPU modules allows a remote unauthenticated attacker to cause a denial of service (DoS) condition or execute malicious code on a target product by sending specially crafted packets. A system reset of the product is required for recovery from a denial of service (DoS) condition and malicious code execution. | |||||
CVE-2022-29830 | 1 Mitsubishielectric | 1 Gx Works3 | 2023-06-29 | N/A | 9.1 CRITICAL |
Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.095Z and Motion Control Setting(GX Works3 related software) versions from 1.000A and later allows a remote unauthenticated attacker to disclose or tamper with sensitive information. As a result, unauthenticated attackers may obtain information about project files illegally. | |||||
CVE-2022-25164 | 1 Mitsubishielectric | 2 Gx Works3, Mx Opc Ua Module Configurator-r | 2023-06-29 | N/A | 7.5 HIGH |
Cleartext Storage of Sensitive Information vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.095Z and Mitsubishi Electric MX OPC UA Module Configurator-R versions 1.08J and prior allows a remote unauthenticated attacker to disclose sensitive information. As a result, unauthenticated attackers can gain unauthorized access to the MELSEC CPU module and the MELSEC OPC UA server module. | |||||
CVE-2022-29827 | 1 Mitsubishielectric | 1 Gx Works3 | 2023-06-29 | N/A | 7.5 HIGH |
Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A and later allows a remote unauthenticated attacker to disclose sensitive information. As a result, unauthenticated attackers may view programs and project files or execute programs illegally. |