Filtered by vendor Softing
Subscribe
Total
44 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2022-1373 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2023-06-27 | N/A | 7.2 HIGH |
The “restore configuration” feature of Softing Secure Integration Server V1.22 is vulnerable to a directory traversal vulnerability when processing zip files. An attacker can craft a zip file to load an arbitrary dll and execute code. Using the "restore configuration" feature to upload a zip file containing a path traversal file may cause a file to be created and executed upon touching the disk. | |||||
CVE-2022-2336 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-22 | N/A | 9.8 CRITICAL |
Softing Secure Integration Server, edgeConnector, and edgeAggregator software ships with the default administrator credentials as `admin` and password as `admin`. This allows Softing to log in to the server directly to perform administrative functions. Upon installation or upon first login, the application does not ask the user to change the `admin` password. There is no warning or prompt to ask the user to change the default password, and to change the password, many steps are required. | |||||
CVE-2022-2334 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.2 HIGH |
The application searches for a library dll that is not found. If an attacker can place a dll with this name, then the attacker can leverage it to execute arbitrary code on the targeted Softing Secure Integration Server V1.22. | |||||
CVE-2022-1748 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.5 HIGH |
Softing OPC UA C++ Server SDK, Secure Integration Server, edgeConnector, edgeAggregator, OPC Suite, and uaGate are affected by a NULL pointer dereference vulnerability. | |||||
CVE-2022-2338 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 5.3 MEDIUM |
Softing Secure Integration Server V1.22 is vulnerable to authentication bypass via a machine-in-the-middle attack. The default the administration interface is accessible via plaintext HTTP protocol, facilitating the attack. The HTTP request may contain the session cookie in the request, which may be captured for use in authenticating to the server. | |||||
CVE-2022-2335 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.5 HIGH |
A crafted HTTP packet with a -1 content-length header can create a denial-of-service condition in Softing Secure Integration Server V1.22. | |||||
CVE-2022-2337 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.5 HIGH |
A crafted HTTP packet with a missing HTTP URI can create a denial-of-service condition in Softing Secure Integration Server V1.22. | |||||
CVE-2022-2547 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.5 HIGH |
A crafted HTTP packet without a content-type header can create a denial-of-service condition in Softing Secure Integration Server V1.22. | |||||
CVE-2022-1069 | 1 Softing | 6 Edgeaggregator, Edgeconnector, Opc and 3 more | 2022-08-19 | N/A | 7.5 HIGH |
A crafted HTTP packet with a large content-length header can create a denial-of-service condition in Softing Secure Integration Server V1.22. | |||||
CVE-2021-32994 | 1 Softing | 1 Opc Ua C\+\+ Software Development Kit | 2022-04-13 | 5.0 MEDIUM | 7.5 HIGH |
Softing OPC UA C++ SDK (Software Development Kit) versions from 5.59 to 5.64 exported library functions don't properly validate received extension objects, which may allow an attacker to crash the software by sending a variety of specially crafted packets to access several unexpected memory locations. | |||||
CVE-2021-42262 | 1 Softing | 3 Datafeed Opc Suite, Opc Ua C\+\+ Software Development Kit, Secure Integration Server | 2022-03-18 | 4.0 MEDIUM | 6.5 MEDIUM |
An issue was discovered in Softing OPC UA C++ SDK before 5.70. An invalid XML element in the type dictionary makes the OPC/UA client crash due to an out-of-memory condition. | |||||
CVE-2021-42577 | 1 Softing | 3 Datafeed Opc Suite, Opc Ua C\+\+ Software Development Kit, Secure Integration Server | 2022-03-18 | 5.0 MEDIUM | 7.5 HIGH |
An issue was discovered in Softing OPC UA C++ SDK before 5.70. A malformed OPC/UA message abort packet makes the client crash with a NULL pointer dereference. | |||||
CVE-2021-40872 | 1 Softing | 2 Smartlink Hw-dp, Uatoolkit Embedded | 2021-11-16 | 5.0 MEDIUM | 7.5 HIGH |
An issue was discovered in Softing Industrial Automation uaToolkit Embedded before 1.40. Remote attackers to cause a denial of service (DoS) or login as an anonymous user (bypassing security checks) by sending crafted messages to a OPC/UA server. The server process may crash unexpectedly because of an invalid type cast, and must be restarted. | |||||
CVE-2021-40873 | 1 Softing | 7 Datafeed Opc Suite, Edgeconnector, Opc and 4 more | 2021-11-16 | 5.0 MEDIUM | 7.5 HIGH |
An issue was discovered in Softing Industrial Automation OPC UA C++ SDK before 5.66, and uaToolkit Embedded before 1.40. Remote attackers to cause a denial of service (DoS) by sending crafted messages to a client or server. The server process may crash unexpectedly because of a double free, and must be restarted. | |||||
CVE-2021-40871 | 1 Softing | 4 Datafeed Opc Suite, Opc, Secure Integration Server and 1 more | 2021-11-16 | 5.0 MEDIUM | 7.5 HIGH |
An issue was discovered in Softing Industrial Automation OPC UA C++ SDK before 5.66. Remote attackers to cause a denial of service (DoS) by sending crafted messages to a OPC/UA client. The client process may crash unexpectedly because of a wrong type cast, and must be restarted. | |||||
CVE-2020-14524 | 1 Softing | 1 Opc | 2021-09-23 | 7.5 HIGH | 9.8 CRITICAL |
Softing Industrial Automation all versions prior to the latest build of version 4.47.0, The affected product is vulnerable to a heap-based buffer overflow, which may allow an attacker to remotely execute arbitrary code. | |||||
CVE-2019-11528 | 1 Softing | 2 Uagate Si, Uagate Si Firmware | 2021-07-21 | 5.0 MEDIUM | 7.5 HIGH |
An issue was discovered in Softing uaGate SI 1.60.01. A system default path for executables is user writable. | |||||
CVE-2019-11526 | 1 Softing | 2 Uagate Si, Uagate Si Firmware | 2021-07-21 | 10.0 HIGH | 9.8 CRITICAL |
An issue was discovered in Softing uaGate SI 1.60.01. A maintenance script, that is executable via sudo, is vulnerable to file path injection. This enables the Attacker to write files with superuser privileges in specific locations. | |||||
CVE-2021-29660 | 1 Softing | 1 Opc Toolbox | 2021-04-08 | 6.8 MEDIUM | 8.8 HIGH |
A Cross-Site Request Forgery (CSRF) vulnerability in en/cfg_setpwd.html in Softing AG OPC Toolbox through 4.10.1.13035 allows attackers to reset the administrative password by inducing the Administrator user to browse a URL controlled by an attacker. | |||||
CVE-2021-29661 | 1 Softing | 1 Opc Toolbox | 2021-04-08 | 3.5 LOW | 5.4 MEDIUM |
Softing AG OPC Toolbox through 4.10.1.13035 allows /en/diag_values.html Stored XSS via the ITEMLISTVALUES##ITEMID parameter, resulting in JavaScript payload injection into the trace file. This payload will then be triggered every time an authenticated user browses the page containing it. |